AVAILABLE EFX TMVS
|
Incoming Pressure To Valve
|
|
|
Part #
|
30 PSI
|
45 PSI
|
60 PSI
|
Pressure Drop Thru Valve
|
|
S19-2000 (Technical Data)
|
7.8 GPM
|
9.4 GPM
|
11.6 GPM
|
PSI
|
|
S19-2100 (Technical Data)
|
36 GPM
|
44 GPM
|
50 GPM
|
PSI
|
|
S19-2200 (Technical Data)
|
67 GPM
|
83 GPM
|
95 GPM
|
PSI
|
|
S19-2300 (Technical Data)
|
103 GPM
|
127 GPM
|
148 GPM
|
PSI
|
|
|
|
|
|
|
|
To purchase one of the products above, please find your nearest Bradley Sales
Location.
|
|
|
|
|
|
Key information for sizing Thermostatic Mixing Valves for Emergency Fixtures:
|
|
- Determine incoming pressure. Valve flow depends on pressure supplied to valve.
- Per ANSI, a minimum of 30 PSI must be supplied to Emergency Eyewash and Shower Equipment.
- To use a TMV, a minimum of 2 GPM must be supplied to the unit.
- EFX items should be on a dedicated supply line so supply will not be disrupted.
- The number of units attached to a Thermostatic Mixing Valve will depend on location and flow requirements.
- The layout of TMVs must be determined by end user, or installer/plumber.
- If calculated amount is higher than valve GPM rating at incoming pressure, additional valves must
be used.
|

|