BRADLEY HALO EMERGENCYPLUMBING FIXTURES

Bradley Halo Emergency Plumbing Fixturesare a new generation in safety equipment, featuring separate supplyand waste piping to eye/face wash, ergonomic hand activation paddleeasy to reach from any direction, and instant water flow on openingthe new translucent dust cover. Halo eye/face wash units providefull face water distribution profile recognized as the best design inthe industry. Anti-microbial protection, integral strainers, andBradley's unique patented self-draining design all reduce thepotential for bacteria growth, providing safer, more effectivefixtures.

Halo units are available in pedestal,wall-mount, and combination units.

Bradley Corporation, the industry's leadingmanufacturer of premium quality commercial lavatories and lavatoryfaucets, wash stations, toilet accessories, and emergency plumbingfixtures, serves a diverse customer base ranging from local businessfacilities to international corporations like Wal-Mart, GeneralMotors, U.S. Postal Service, W.W. Grainger, AMC Theaters Corporation.

Architects, engineers, and specifiers look toBradley Corporation for innovation in design and leadership in thedevelopment of environmentally conscious products. BradleyCorporation, a member of the U.S. Green Building Council, theWisconsin Green Building Alliance, has several products earningcertification by Greenguard Environmental Institute, and GreenguardChildren and Schools program.

Bradley eases the specifying process with aseasoned customer service staff and a range of helpful informationtools on an advanced website. For example, easy-to-use sizingsoftware, available on Bradley's website, allows engineers to quicklydetermine the correct size Thermostatic Mixing Valves.

Bradley is the industry leader in themanufacture of premium quality commercial plumbing fixtures, valves,TMVs and washroom accessories that appear in the following CSIMasterFormat 2004™ Sections:

Section 10 21 13 – ToiletCompartments (Mills Metal, Plastic-laminate, Phenolic, and Plasticunits)

Section 10 28 13.13 –Commercial Toilet Accessories

Section 10 28 13.15 – Handand Hair Dryers

Section 10 28 13.63 –Detention Toilet Accessories

Section 10 51 26.00 –Plastic Lockers (Lenox Plastic Lockers)

Section 10 51 26.13 –Plastic Lockers (Lenox Recycled Plastic lockers)

Section 22 11 19 –Domestic Water Piping Specialties (Thermostatic mixing valves)

Section 22 42 16.01 –Commercial Lavatories and Faucets (Single and multi-station lavatorysystems)

Section 22 42 16.02 –Commercial Lavatories and Faucets (Bradley Advocate Lavatory System)

Section 22 42 16.03 –Commercial Lavatories and Faucets (Bradley Verge Lavatory System)

Section 22 42 16.11 –Commercial Sinks and Faucets

Section 22 42 23 –Commercial Showers and Shower Valves

Section 22 42 33 – WashFountains

Section 22 43 00 –Healthcare Plumbing Fixtures (Patient care lavatory units)

Section 22 45 00 –Emergency Plumbing Fixtures (EmergencyEyewash Fixtures and Drench Showers)

Section 22 46 00 –Security Plumbing Fixtures

Contact Bradley Corporation, Menomonee Falls,WI 53051; Phone: 800-BRADLEY ((800)272-3539) Fax: (262)251-5817, orvisit the Bradley web site www.bradleycorp.com.

Bradley Corporation is an AIA/CES registeredprovider currently offering five programs earning one (1) HS&WLearning Unit each; several qualify for sustainable design (SD)credit. All active AIA members must successfully complete 18learning unit (LU) hours each year.

SECTION 22 45 00 – EMERGENCY PLUMBING FIXTURES

PART 1 - GENERAL

1.1SECTION INCLUDES

1.Pedestal-mountedeyewash and eye/face wash equipment.

2.Wall-mounted eyewashand eye/face wash equipment.

3.Combination emergencyshower and eyewash units.

4.Water-temperingequipment.

1.2RELATED SECTIONS

A.Division22 Section "Sanitary Waste Piping Specialties" for floordrains.

1.3REFERENCES

A.AmericanNational Standards Institute (ANSI):

1.ANSIZ 358.1 – American National Standard for Emergency Eyewash andShower Equipment.

B.USFederal Government:

1.PublicLaw 90-480 – The Architectural Barriers Act of 1968, asamended.

2.Public Law 101-336 –The Americans with Disabilities Act of 1990, as amended.

1.4ACTION SUBMITTALS

A.ProductData: For each product:

1.Manufacturer'sdata sheets indicating operating characteristics, materials andfinishes.

2.Include details ofelectrical and mechanical operating parts.

3.Provide mountingrequirements and rough-in dimensions.

4.Mark each sheet withproduct drawing designation.

B.ShopDrawings: Submit power, signal, and control wiring diagrams.

1.5INFORMATION SUBMITTALS

A.Manufacturer'sCertificates: Submit certificates documenting factory testing ofspecified units.

B.Fieldquality-control test reports.

1.6CLOSEOUT SUBMITTALS

A.Operationand maintenance data.

1.7MAINTENANCE SUBMITTALS

A.Furnishindicated spare parts that are packaged with identifying labelslisting associated products.

1.8QUALITY ASSURANCE

A.SourceLimitations: Obtain emergency plumbing fixtures through a singlesource from a single manufacturer.

B.ANSIStandard: Comply with ANSI Z358.1.

C.NSFStandard: Comply with NSF 61 for fixture components in contactwith potable water.

D.AccessibilityRequirements: Comply with ICC/ANSI A117.1;[Public Law 90-480 and Public Law 101-336]and requirements of authorities having jurisdiction.

PART 2 - PRODUCTS

2.1MANUFACTURERS

A.Basis-of-DesignProduct: Subject to compliance with requirements, provide emergencyplumbing fixtures manufactured by Bradley Corporation,Menomonee Falls, WI 53051, (800)272-3539, fax (262)251-5817; Emailinfo@BradleyCorp.com; Website www.bradleycorp.com.

Specifier: Retain one of three paragraphsbelow based upon Project requirements.

1.Submitcomparable products of one of the following for approval byArchitect:

a.[Specifier: Insert name of manufacturer of comparable product.]

2.Submitrequests for substitution in accordance with Instructions to Biddersand Division 01 General Requirements.

3.Provide specifiedproduct; Owner will not consider substitution requests.

2.2PEDESTAL-MOUNTED EMERGENCY PLUMBING FIXTURES

A.Accessible,Pedestal-Mounted, Plumbed Eyewash Units EPF#___: ANSI Z358.1,self-draining, with separate supply and waste piping. Providefactory-assembled and tested units with standard-compliantidentification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Pedestal-Mount HaloEyewash S19214 Series.

2.Eyewash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

3.Ball Valve: NPT1/2-inch (DN 15), [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass self-closingwash valve].

4.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [, andaluminum foot pedal] [,and stainless steel foot pedal].

5.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

6.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

7.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

8.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

9.Water TemperingEquipment: Thermostatic mixing valve assembly TMV#01.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

10.Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

11.Scald ProtectionEquipment: Anti-scald valve.

12.Flow Switch Alarm: Waterproof NEMA No 3R, automatic audible and visual system withremote wiring contacts, CSA-listed flow switch [120VAC, 1.75A] [120/24VAC transformer, 1.25A], and1-1/4-inch NPT supply.

13.Explosion Proof FlowSwitch Alarm: automatic audible and visual system with remote wiringcontacts, CSA-listed flow switch [ClassI, Division II Groups B, C and D explosion proof][Class I, Division I Groups C andD explosion proof], [120VAC, 0.5A] [220VAC, 0.5A], and 1-1/4-inch NPTsupply.

B.Accessible,Pedestal-Mounted, Plumbed Eye/Face Wash Units EPF#___: ANSIZ358.1, self-draining, with separate supply and waste piping. Provide factory-assembled and tested units with standard-compliantidentification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Pedestal-Mount HaloEye/Face Wash S19214 Series.

2.Eye/Face Wash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

3.Ball Valve: NPT1/2-inch (DN 15), [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass self-closingwash valve].

4.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [, andaluminum foot pedal] [,and stainless steel foot pedal].

5.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

6.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

7.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

8.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

1)Water TemperingEquipment: Thermostatic mixing valve assembly TMV#01.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

9.Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

10.Scald ProtectionEquipment: Anti-scald valve.

11.Flow Switch Alarm: automatic audible and visual system with remote wiring contacts,CSA-listed flow switch [120 VAC,1.75A] [120/24VAC transformer, 1.25A], and1/2-inch NPT supply.

12.Explosion Proof FlowSwitch Alarm: automatic audible and visual system with remote wiringcontacts, CSA-listed flow switch [ClassI, Division II Groups B, C and D explosion proof][Class I, Division I Groups C andD explosion proof], [120VAC, 0.5A] [220VAC, 0.5A], and 1/2-inch NPTsupply.

2.3WALL-MOUNTED EMERGENCY PLUMBING FIXTURES

A.Accessible,Wall-Mounted, Plumbed Eyewash Units EPF#___: ANSI Z358.1,self-draining, with separate supply and waste piping. Providefactory-assembled and tested units with standard-compliantidentification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Wall-Mount Halo EyewashS19224 Series.

2.Eyewash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

3.Ball Valve: NPT1/2-inch (DN 15), [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass self-closingwash valve].

4.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [,and stainless steel foot pedal].

5.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass][, including tailpiece and p-trap].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

6.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

7.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

8.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

9.Water TemperingEquipment: Thermostatic mixing valve assembly TMV#01.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

10.Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

11.Scald ProtectionEquipment: Anti-scald valve.

12.Flow Switch Alarm: Waterproof NEMA No 3R, UL-listed and CSA approved automatic audibleand visual system with remote wiring contacts, [120VAC, 1.75A] [120/24VAC transformer, 1.25A], and1-1/4-inch NPT supply.

13.Explosion Proof FlowSwitch Alarm: Waterproof NEMA No 4, UL-listed and CSA approvedautomatic audible and visual system with remote wiring contacts,[Class I, Division II Groups B, Cand D explosion proof] [ClassI, Division I Groups C and D explosion proof],[120 VAC, 0.5A][220 VAC, 0.5A],and 1/2-inch NPT supply.

B.Accessible,Wall-Mounted, Plumbed Eye/Face Wash Units EPF#___: ANSIZ358.1, self-draining, with separate supply and waste piping. Provide factory-assembled and tested units with standard-compliantidentification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Wall-Mount Halo Eye/FaceWash S19224 Series.

2.Eye/Face Wash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

3.Ball Valve: NPT1/2-inch (DN 15), [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass self-closingwash valve].

4.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [,and stainless steel foot pedal].

5.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass][, including tailpiece and p-trap].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

6.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

7.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

8.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

9.Water TemperingEquipment: Thermostatic mixing valve assembly TMV#01.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

10.Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

11.Scald ProtectionEquipment: Anti-scald valve.

12.Flow Switch Alarm: Waterproof NEMA No 3R, automatic audible and visual system withremote wiring contacts, CSA-listed flow switch [120VAC, 1.75A] [120/24VAC transformer, 1.25A], and1/2-inch NPT supply.

13.Explosion Proof FlowSwitch Alarm: automatic audible and visual system with remote wiringcontacts, CSA-listed flow switch [ClassI, Division II Groups B, C and D explosion proof][Class I, Division I Groups C andD explosion proof], [120VAC, 0.5A] [220VAC, 0.5A], and 1/2-inch NPTsupply.

2.4COMBINATION EMERGENCY PLUMBING FIXTURES

A.Standard,Plumbed Emergency Shower with Eyewash Combination Units EPF#___: ANSI Z358.1, self-draining, with separate supply and waste piping. Provide factory-assembled and tested units with standard-compliantidentification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Pedestal-Mount HaloEyewash S19314 Series.

2.Eyewash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

Specifier: Select standard plastic or highperformance stainless steel showerhead below. Bradley's patentedSpinTec showerhead technology provides maximum water distributionwhile providing consistent water flow.

3.Showerhead: 26 gpm(1.45 L/s) flow rate, 3.1-inch (78.1 mm) diameter yellowimpact-resistant plastic head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

4.Showerhead: 26 gpm(1.45 L/s) flow rate, 2-inch (51 mm) diameter [Type304] [Type316] stainless steel head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

5.Ball Valves: NPT1-inch (DN 25) shower valve andNPT 1/2-inch (DN15) eyewash valve, [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass stay-openeyewash valve and self-closing shower valve].

6.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [, andaluminum foot pedal] [,and stainless steel foot pedal].

7.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

8.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

9.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

10.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

11.Water TemperingEquipment: Thermostatic mixing valve assembly TMV#02.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

12.Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

13.Scald ProtectionEquipment: Anti-scald valve.

14.Flow Switch Alarm: Waterproof NEMA No 3R, automatic audible and visual system withremote wiring contacts, CSA-listed flow switch [120VAC, 1.75A] [120/24VAC transformer, 1.25A], and1-1/4-inch NPT supply.

15.Explosion Proof FlowSwitch Alarm: Waterproof NEMA No 4, automatic audible and visualsystem with remote wiring contacts, CSA-listed flow switch [ClassI, Division II Groups B, C and D explosion proof][Class I, Division I Groups C andD explosion proof], [120VAC, 0.5A] [220VAC, 0.5A], and 1-1/4-inch NPTsupply.

B.Accessible,Plumbed Emergency Shower with Eyewash Combination Units EPF#___: ANSI Z358.1, self-draining, with separate supply and waste piping. Provide factory-assembled and tested units with standard-compliantidentification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Pedestal-Mount HaloAccessible Eyewash S19314 Series.

2.Eyewash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

Specifier: Select standard plastic or highperformance stainless steel showerhead below. Bradley's patentedSpinTec showerhead technology provides maximum water distributionwhile providing consistent water flow.

3.Showerhead: 26 gpm(1.45 L/s) flow rate, 3.1-inch (78.1 mm) diameter yellowimpact-resistant plastic head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

4.Showerhead: 26 gpm(1.45 L/s) flow rate, 2-inch (51 mm) diameter [Type304] [Type316] stainless steel head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

5.Ball Valves: NPT1-inch (DN 25) shower valve andNPT 1/2-inch (DN15) eyewash valve, [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass stay-openeyewash valve and self-closing shower valve].

6.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [,and accessible pull rod].

7.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

8.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

9.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

10.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

11.Water TemperingEquipment: Thermostatic mixing valve assembly TMV#02.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

12.Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

13.Scald ProtectionEquipment: Anti-scald valve.

14.Flow Switch Alarm: Waterproof NEMA No 3R, automatic audible and visual system withremote wiring contacts, CSA-listed flow switch [120VAC, 1.75A] [120/24VAC transformer, 1.25A], and1-1/4-inch NPT supply.

15.Explosion Proof FlowSwitch Alarm: Waterproof NEMA No 4, UL-listed and CSA approvedautomatic audible and visual system with remote wiring contacts,[Class I, Division II Groups B, Cand D explosion proof] [ClassI, Division I Groups C and D explosion proof],[120 VAC, 0.5A][220 VAC, 0.5A],and 1-1/4-inch NPT supply.

C.Standard,Plumbed Emergency Shower with Eye/Face Wash Combination UnitsEPF#___: ANSI Z358.1, self-draining, with separate supply andwaste piping. Provide factory-assembled and tested units withstandard-compliant identification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Pedestal-Mount HaloEye/Face Wash S19314 Series.

2.Eye/Face Wash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

Specifier: Select standard plastic or highperformance stainless steel showerhead below. Bradley's patentedSpinTec showerhead technology provides maximum water distributionwhile providing consistent water flow.

3.Showerhead: 26 gpm(1.45 L/s) flow rate, 3.1-inch (78.1 mm) diameter yellowimpact-resistant plastic head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

4.Showerhead: 26 gpm(1.45 L/s) flow rate, 2-inch (51 mm) diameter [Type304] [Type316] stainless steel head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

5.Ball Valves: NPT1-inch (DN 25) shower valve andNPT 1/2-inch (DN15) eye/face wash valve, [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass stay-openeye/face wash valve and self-closing shower valve].

6.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [, andaluminum foot pedal] [,and stainless steel foot pedal].

7.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

8.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

9.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

10.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

11.Water TemperingEquipment: Thermostatic mixing valve assembly TMV#02.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

12.Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

13.Scald ProtectionEquipment: Anti-scald valve.

14.Flow Switch Alarm: Waterproof NEMA No 3R, automatic audible and visual system withremote wiring contacts, CSA-listed flow switch [120VAC, 1.75A] [120/24VAC transformer, 1.25A], and1-1/4-inch NPT supply.

15.Explosion Proof FlowSwitch Alarm: automatic audible and visual system with remote wiringcontacts, CSA-listed flow switch [ClassI, Division II Groups B, C and D explosion proof][Class I, Division I Groups C andD explosion proof], [120VAC, 0.5A] [220VAC, 0.5A], and 1-1/4-inch NPTsupply.

D.Accessible,Plumbed Emergency Shower with Eye/Face Wash Combination UnitsEPF#___: ANSI Z358.1, self-draining, with separate supply andwaste piping. Provide factory-assembled and tested units withstandard-compliant identification sign and inspection tag.

1.Basisof Design Manufacturer/Model: Bradley, Pedestal-Mount HaloAccessible Eye/Face Wash S19314 Series.

2.Eye/Face Wash: 4.3gpm (0.271 L/s), with integralanti-microbial agent.

Specifier: Select standard plastic or highperformance stainless steel showerhead below. Bradley's patentedSpinTec showerhead technology provides maximum water distributionwhile providing consistent water flow.

3.Showerhead: 26 gpm(1.45 L/s) flow rate, 3.1-inch (78.1 mm) diameter yellowimpact-resistant plastic head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

4.Showerhead: 26 gpm(1.45 L/s) flow rate, 2-inch (51 mm) diameter [Type304] [Type316] stainless steel head [withyellow impact-resistant plastic shroud][with stainless steel shroud].

5.Ball Valves: NPT1-inch (DN 25) shower valve andNPT 1/2-inch (DN15) eye/face wash valve, [chrome-platedbrass stay-open wash valve] [Type316 stainless steel stay-open wash valve][chrome-plated brass stay-openeye/face wash valve and self-closing shower valve].

6.Valve Operation: Hand-activated push handle, [Type304 stainless steel] [Type316 stainless steel] [, andaccessible pull rod].

7.Pipe and Fittings: NPT1-1/4-inch (DN 32) diameter,[galvanized steel with epoxysafety yellow coating] [Type304 stainless steel] [Type316 stainless steel][chrome-plated red brass].

Specifier: Bowl, dust cover, drench hose, andwater tempering items below are available options from Bradley.

8.Bowl: [Yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel],with integral strainer.

9.Dust Cover: [Eyewashcover] [Fullbowl activating cover], [yellowtransparent plastic] [Type304 Stainless steel] [Type316 Stainless steel].

10.Drench Hose: 8-foot(2438 mm) yellow reinforced thermoplastic hose with 3/8-inchNPT male thread, withchrome-plated brass stay-open valve, [withvacuum breaker] [withbackflow preventer], attachmentsupply, fittings, and hangar, equipped with ABS plastic sprayhead andcover.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

1)Water TemperingEquipment: Thermostatic mixing valve assembly TMV#02.

Specifier: Anti-freeze valve drains pipingwhere unit may be exposed to freezing conditions.

2)Freeze ProtectionEquipment: Anti-freeze valve.

Specifier: Anti-scald valve drains piping whenunit may be exposed to temperatures in excess of 85 deg. F.

3)Scald ProtectionEquipment: Anti-scald valve.

4)Flow Switch Alarm: Waterproof NEMA No 3R, automatic audible and visual system withremote wiring contacts, CSA-listed [120VAC, 1.75A] [120/24VAC transformer, 1.25A], and1-1/4-inch NPT supply.

5)Explosion Proof FlowSwitch Alarm: Waterproof NEMA No 4, automatic audible and visualsystem with remote wiring contacts, CSA-listed [ClassI, Division II Groups B, C and D explosion proof][Class I, Division I Groups C andD explosion proof], [120VAC, 0.5A] [220VAC, 0.5A], and 1-1/4-inch NPTsupply.

Specifier: Thermostatic mixing valve assemblyis recommended by Bradley as best way to satisfy ANSI Z358.1requirement for providing tepid water delivery to emergency plumbingfixtures.

2.5WATER TEMPERING EQUIPMENT

A.ThermostaticMixing Valve for Eyewash and Eye/Face Wash Units TMV#01: ANSIZ358.1 compliant single valve design with liquid-filled unit-mounteddial thermometer, providing 85 deg F(29 deg C) tepid, potable water, maintaining temperatureat plus or minus 5 deg F(3 deg C) for required 15-minute test period, and in caseof unit failure to continue cold-water flow, with associatedcorrosion-resistant housing and fittings.

1.Basisof Design Manufacturer/Model: Bradley, Navigator EmergencyThermostatic Mixing Valve S19-2000 EFX-8.

2.Supply Connections: Hot and cold water.

3.Flow Capacity: 8 gpmat 30 psi (34 L/s at 2.5 kPa).

4.Finish: [Roughbronze] [Chrome-platedbronze].

5.Cabinet: [Surfacemounted stainless steel][Recessed stainless steel][Surface mounted white enamel][Recessed white enamel][Plexiglass window in door],with cylinder door lock.

B.ThermostaticMixing Valve for Combination Shower Units TMV#02: ANSI Z358.1compliant single valve design with liquid-filled unit-mounted dialthermometer, providing 85 deg F(29 deg C) tepid, potable water, maintaining temperatureat plus or minus 5 deg F(3 deg C) for required 15-minute test period, and in caseof unit failure to continue cold-water flow, with associatedcorrosion-resistant housing and fittings.

1.Basisof Design Manufacturer/Model: Bradley, Navigator EmergencyThermostatic Mixing Valve S19-2100 EFX-25.

2.Supply Connections: Hot and cold water.

3.Flow Capacity: 36 gpmat 30 psi ( L/s at kPa).

4.Finish: [Roughbronze] [Chrome-platedbronze].

5.Cabinet: [Surfacemounted stainless steel][Recessed stainless steel][Surface mounted white enamel][Recessed white enamel][Plexiglass window in door],with cylinder door lock.

PART 3 - EXECUTION

3.1INSTALLATION

A.Assemblefixtures and associated fittings and trim in accordance withmanufacturer's instructions.

B.Installfixture supports attached to building structure for fixturesrequiring supports.

C.Installfixtures onto waste-fitting seals or flanges and attach to supportsor building structure.

D.Installfixtures level, plumb, and firmly in place in accordance withmanufacturer's rough-in drawings.

E.Installwater supply piping to each fixture requiring water supplyconnection. Provide stop on each supply in readily-serviced location.Fasten supply piping to supports or substrate.

F.Installtrap and waste piping to each fixture requiring sanitary systemconnection.

G.Installescutcheons at exposed piping penetrations in finished locations andwithin cabinets.

H.Sealjoints between fixtures and walls, floors, and countertops withmildew-resistant silicone sealant.

3.2CLEANING AND PROTECTION

A.Repairor replace defective work, including damaged fixtures and components.

B.Cleanunit surfaces, test fixtures, and leave in ready-to-use condition.

C.Turnover keys, tools, maintenance instructions, and maintenance stock toOwner.

D.Protectunits with water-resistant temporary covering. Do not allow temporaryuse of plumbing fixtures unless approved in writing by Architect.Remove protection at Substantial Completion and dispose.

3.3TESTING AND ADJUSTING

A.Setfield-adjustable temperature set points of temperature-actuated watermixing valves. Adjust set point within allowable temperature range.

B.Testand adjust installation.

C.Removeand replace malfunctioning thermostatic mixing valves and retest.

ENDOF SECTION

BRADLEY CORPORATION 22 45 00 EMERGENCY PLUMBING FIXTURES

<Page 13 of 13>